- Python 77.5%
- JavaScript 19.7%
- CSS 2.4%
- HTML 0.2%
- Shell 0.2%
| Filename | Latest commit message | Latest commit date |
|---|---|---|
Spec -> topology generator -> NetBox model, draw.io, BOM, cable map, IP plan, Blender renders and the Fabric Atlas configurator. Three designs: 2-SU H200, GB300 NVL72 SU, mixed liquid pod. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_012VhweeGBN67HAX7HxehgBw |
||
| .github/workflows | ||
| bin | ||
| blender | ||
| catalog | ||
| docs | ||
| reference | ||
| spec | ||
| src/dgxnb | ||
| tests | ||
| viewer/atlas | ||
| .gitignore | ||
| .python-version | ||
| cliff.toml | ||
| LICENSE | ||
| NOTICE | ||
| pyproject.toml | ||
| README.md | ||
| uv.lock | ||
DGX SuperPOD as code
A reference-faithful design of NVIDIA DGX SuperPODs, written as data and generated into everything an architect needs to review or build from: a NetBox model, draw.io drawings, rack elevations, a bill of materials, a cable map, an IP plan and photoreal 3D renders.
The problem
Designing a 500-GPU-class SuperPOD from NVIDIA's reference architecture means getting several interlocking things right at once, and keeping them right when a number changes:
- Four networks. A rail-optimised InfiniBand compute fabric (8 rails per node), a storage fabric, an in-band Ethernet network and a 1 GbE out-of-band network, each with its own switch counts, oversubscription rules and cable types.
- Power. Three discrete power paths per rack, rPDU-to-PSU mapping, per-rack budgets against the reference circuit sizes.
- Cooling. Hot-aisle containment for air-cooled H200, rear-door heat exchangers and direct liquid for GB300 NVL72, with CDUs and a plant.
- Racks and hall. Rack-unit placement, rack counts, aisle widths and cable paths.
A spreadsheet drifts. A drawing goes stale. This repo derives all of them from one source.
Approach
spec/*.yaml -> topology generator (src/dgxnb) -> NetBox (source of truth, optional)
-> draw.io pages, rack elevations
-> BOM, cable map, IP plan, NVIDIA Air topology
-> scene.json -> Blender renders
- The spec holds the choices (SU count, GPU generation, storage tiers, power, hall layout).
Every sizing number cites its section of the reference architecture in
docs/ra-notes*.md; every judgement call is labelled CHOICE with its reason indocs/design-choices.md. - The generator is a pure function from spec to a desired-state model, tested offline.
- A reconciler applies that model to a NetBox instance idempotently by natural key, and prunes only what it owns. NetBox is optional: every output below is generated without it.
- Unsourced values are listed, with what was used and where to look, in
docs/not-found.md.
What the model enforces
The offline tests (tests/) and the live validator (bin/validate, needs a NetBox) check, among
others:
- node, GPU, switch and rack counts equal the reference architecture's scale tables (1 to 4 SUs);
- every DGX has 8 compute cables to 8 distinct leaf switches, one per rail, and each leaf serves one rail only;
- no leaf has more downlinks than uplinks (non-blocking fat tree);
- every cable has two terminations and no port is cabled twice;
- every DGX PSU lands on a free outlet of the right type, two PSUs per rPDU, three power paths;
- peak draw per rack stays inside its budget;
- no two devices overlap in a rack, and nothing exceeds the rack height;
- the generated output is deterministic.
The three designs
| Design | Spec | Compute | Racks | Cables |
|---|---|---|---|---|
| 2-SU DGX H200 (reference architecture RA-11336-001) | spec/superpod.yaml |
63 DGX H200 = 504 GPUs | 38 | 2,445 |
| 1-SU DGX GB300 NVL72 | spec/gb300-su.yaml |
8 NVL72 racks, 144 trays = 576 GPUs | 12 | 3,876 |
| Mixed liquid pod: 1 SU H200 with rear-door heat exchangers + 1 SU GB300 on direct liquid, one cooling plant | spec/superpod-mixed.yaml |
31 DGX + 144 trays = 824 GPUs | 33 | 5,310 |
The generator's cable count includes the power cords (about 620 for the H200 design) and the storage and management cabling it models in full; the Fabric Atlas counts a narrower scope, data cables only (compute, storage, in-band, out-of-band) without power cords, from its own sizing rules. For the same 2-SU H200 the Atlas reports 1,812 cables and 35 racks against the generator's 2,445 and 38, so the numbers differ by design.
Outputs for the H200 design are in docs/; the other two are in docs/dgx-gb300-su/ and
docs/dgx-superpod-mixed/. Each has a draw.io file (open in diagrams.net), a cable map CSV, a BOM,
an IP plan and an NVIDIA Air topology.
Fabric Atlas
A single-file configurator for DGX SuperPODs from H100 to GB300: pick generation, cooling, SU count and workload, and get live GPU, switch, cable, rack and power counters, topology, rack elevations and a BOM where each line is tagged RA, DERIVED, CHOICE or NON-RA. It runs entirely in the browser; saved scenarios use local storage.
Build it with python3 viewer/atlas/build.py (output: viewer/dist/fabric-atlas.html).
Run it offline
uv run pytest # generator tests (no NetBox needed)
node --test viewer/atlas/test.mjs # Atlas engine reproduces the RA scale tables
bin/dgxnb export # H200: cable map, BOM, IP plan, draw.io, scene.json
bin/dgxnb export --spec spec/gb300-su.yaml
bin/dgxnb export --spec spec/superpod-mixed.yaml
python3 viewer/atlas/build.py # Fabric Atlas
Python 3.9+ with uv. To apply a design to your own NetBox, set
NETBOX_URL and NETBOX_TOKEN and run bin/dgxnb plan (a read-only diff) before
bin/dgxnb apply. The Blender pipeline is described in blender/README.md.
Design choices
Every place the reference architecture is silent or ambiguous is recorded with the options and the
reason for the pick in docs/design-choices.md. For example: the
rack-unit layout of rPDUs, the tier-1 storage count and its documented alternative, and the
training-first workload assumption.
What this is not
- Not an NVIDIA product, and not endorsed by NVIDIA.
- Not a validated deployment. It is a design exercise that follows the public reference architecture closely; where it had to choose, it says so.
- Not a pricing tool. The BOM counts parts; it does not price them.
- Device-type files for third-party gear are community library definitions or labelled stand-ins;
docs/not-found.mdlists every unsourced value.
Built with Claude Code as a pair programmer; the design choices and review are mine.
Licence
Code: MIT (LICENSE). Documentation and renders: CC BY 4.0 (docs/LICENSE-docs). See NOTICE.